German French Italian Portuguese Japanese Korrean Russian
Home

News

What are the precautions for maintaining an air shower room

What are the precautions for maintaining an air shower room

       Define air shower room:
       It is a general-purpose local purification equipment, people or goods into a clean area, through the fan nozzle spray filtered clean strong wind, blowing away the dust on the surface of people or objects.
      People entering the clean room require a channel, to reduce the people and goods in and out of the large number of dust particles brought about by the installation of a fully functional air valve at the entrance to the clean room can reduce the amount of air pollution. When people and goods through the shower room, pollution particles through the high degree of cleanliness of the clean air are filtered, 25m / s above the high wind speed basically through the coarse and high two-stage filters to filter out the effective jet and drift particles.
      What are the precautions for maintaining the air shower room:
1, if it does not meet the requirements of technical parameters, the regular use of instruments to measure the various technical indicators of the equipment should be dealt with promptly.
2, the primary air filter in the filter media according to the actual use of regular take-down cleaning.
3, when the wind speed is found to become small, the surface of the primary air filter should be checked to see if it is blackened. If it is blackened, it means that the pre-filter has more dust and greater resistance, which means that the non-woven fabric in the primary air filter should be removed for cleaning or replacement.
4, if the non-woven fabric still can not improve the wind speed after replacement or cleaning, it indicates that the air filter has been blocked, resulting in increased resistance, then the air filter should be replaced.
5、When replacing the filter, it is necessary to remove the spray ball plate, take out the filter, and replace the new air filter according to the specification and model of the original filter. When installing, confirm the arrow mark on the filter, the arrow should point to the direction of airflow. And seal well to prevent leakage.
6、After replacing the filter, you should confirm that there is no leakage on the border and test it with a dust particle counter, and it can work normally only after it reaches the technical index.
7、Regular maintenance of the circuit, if there is any fault can refer to the electrical schematic diagram for maintenance.
8、Regular maintenance of the door, so that the electronic lock and its lock hole are aligned to avoid lock pin jamming.