Primary air filter cleaning method and replacement

Primary air filter cleaning method and replacement

When can the primary air filter g3 be cleaned or replaced? When any one of the following three conditions can be met: air conditioning purification system operation, when the value of the differential pressure of the primary and intermediate filters is about two times the value of the initial differential pressure; clean (area) room environment to take formaldehyde fumigation disinfection; air conditioning purification system operation, when the differential pressure of the primary and intermediate filters is lower than the initial value of the differential pressure or no differential pressure


1. Ordinary chemical class: remove the filter paper, gently shake, pour out the dust and foreign matter in the filter bag, soak it with drinking water for no more than 20 minutes, fish it out, and rinse it with drinking water while gently tapping and washing it until the cleaning water is clarified. After flat drying in a clean area, self-study checks the filter bag, if broken, replace the filter bag in time.

2. Cephalosporins: Remove the filter bag, put it into the configured 1% sodium carbonate solution, soak for 10 minutes to inactivate, remove the foreign matter in the bag, rinse with potable water, gently tap the side of the wash until the cleaning water is clarified. After flat drying in the clean area, self-study checks the filter bag, if broken, replace the filter bag in time.

3. Primary and intermediate filters should be cleaned and dried indoors. The filter bag not used for the time being should be cleaned and put into a clean plastic bag for sealing and preservation.

4. The primary and intermediate filters of each workshop should be used exclusively, and should not be used interchangeably. Each workshop's primary and secondary filters should be cleaned, dried, and stored separately.

5. The preliminary and intermediate filters for the production of cephalosporin drugs should be dedicated, not interchangeable or interchangeable with the preliminary and intermediate filters for the production of common chemical drugs.

6. When the clean primary and medium-performance filters are loaded, the initial differential pressure is less than the original initial differential pressure of the filter, the filter bag can not continue to be used and should be eliminated.


Primary air filter g3 cleaning or replacement precautions:

1. When removing or replacing the primary and intermediate filters, the new air valve, the return air valve, and the exhaust fan valve should all be closed.

2. Cleaning can only be done with drinking water, not with brushes.

3. Rinsing is not allowed to use high-pressure water jet rinsing.

4. The end of cleaning can not be too hard to wring the water.