Maintenance and common faults in air showers1. When the air shower is used for a period of time, if the wind speed is very low, the filter of the air shower room should be checked immediately to see if it can accumulate too much dust, such as a new replacement for the filter. Usually 1-6 months it is necessary to exchange once, high efficiency filter is usually 6-12 months exchange once. Maintenance methods for air showers1、regularly use the instrument to determine the technical indicators of the equipment, such as does not meet the requirements of technical parameters should be dealt with in a timely manner. Common faults in air shower rooms1.Power switch, there are usually four places in the air shower room where the power can be cut off:the power switch of the outer cabinet of the air shower room. the control panel of the inner box of the air shower room. air shower room on both sides of the outer box (here the power switch can prevent emergency cut off power, effectively improve our personal safety). When the power indicator does not work, do not prevent re-check the above four wind shower room power supply. 2.When the air shower room fan does not work, the first time to check whether the emergency switch outside the box of the air shower room is cut off, such as to determine the cut off, with a light hand, to the right side of the rotation of the release can be. 3.Air shower room fan reverses or air shower room wind speed is very small, please be sure to check whether the 380V three-phase four-wire line is reversed, the general factory installation will have a dedicated electrician to connect the line; such as reversing the line source of the air shower room, the lighter will cause the air shower room fan does not work or reverses the air shower room wind speed is reduced, the heavier will burn the entire air shower room circuit board; we do not lightly to replace the wiring. 4.Air shower room does not blow shower, in addition to the above three points, but also need to check whether the emergency stop key inside the air shower room box pressed, such as the emergency stop key by colour, the air shower room will not blow shower; to press the emergency stop key again can work normally. 5.Air shower room can not automatically induction blowing shower, check the air shower room in the lower right corner of the box of light-sensing system, see whether the light-sensing device is installed correctly, such as light-sensing two sides are relative and light-sensing normal, then can automatically induction blowing shower. 6.When the wind speed of the air shower room is very low for a period of time, please check whether the primary and high efficiency filters of the air shower room have accumulated too much dust, if so, please replace the filters. (The primary filter of the air shower room is generally replaced within 1-6 months, and the high efficiency filter of the air shower room is generally replaced within 6-12 months) |