I、Power switch.There are usually four places where the power can be cut off in an air shower room.
The power switch in the outer cabinet of the air shower room.
The control panel of the inner box of the air shower room.
On both sides of the outer box of the air shower room (the power switch here prevents the power from being cut off in an emergency, effectively improving the personal safety of staff).
When the power indicator does not work, you may wish to re-check the above several wind shower room power supply.

II、When the air shower room fan does not work.
When the air shower room does not work, the first time to check whether the emergency switch outside the box of the air shower room is cut off, such as to determine the cut off, with a light hand, to the right side of the rotation of the release can be.  

III、Wind shower room fan reverses or the wind speed of the wind shower room is very small, please be sure to check whether the 380V three-phase four-wire line is reversed, the general wind shower room manufacturers will have a dedicated electrician to install a good line;
such as reversing the line source of the wind shower room, the lighter will lead to the wind shower room fan does not work or reverses the wind shower room wind speed reduction, the heavier will burn the entire wind shower room circuit board;
suggest the use of wind shower room enterprises do not lightly replace the wiring, because the production needs to determine to move, please consult the wind shower room manufacturers to solve.
 
IV、The air shower room does not blow the shower, in addition to the above three points, but also need to check whether the emergency stop key inside the air shower room box is pressed, such as the emergency stop key by the color, the air shower room will not blow the shower;
to press the emergency stop key again can work normally.

V、When the air shower room cannot automatically induct the blowing shower, please check the light sensing system in the lower right corner of the box in the air shower room to see if the light sensing device is installed correctly, such as the two sides of the light sensing is relative and the light sensing is normal, it can automatically induct the blowing shower.

VI、When the wind speed of the air shower room is very low for some time, please check whether the primary and high-efficiency filters of the air shower room have accumulated too much dust, if so, please replace the filters. (The primary filter of the air shower room is generally replaced within 1-6 months, and the high-efficiency filter of the air shower room is generally replaced within 6-12 months)