Common faults and solutions of air shower rooms

Common faults and solutions of air shower rooms

     Since the air shower is used frequently and many users do not know how to maintain the air shower, the air shower is prone to malfunctions over time. This article will list the common faults of air showers and explain the principles clearly so that users can query and troubleshoot during use, so that they can quickly solve the problem.
     1. Power switch. There are usually three places where the power can be cut off in the air shower: the power switch of the outdoor box of the air shower; the control panel of the indoor box of the air shower; and the outer boxes on both sides of the air shower (the power switch here can prevent the power from being cut off in an emergency). power supply, effectively improving the personal safety of staff). When the power indicator light is off, you may want to re-check the power supply points of the above three air shower rooms.
     2. When the air shower fan is not working. When the air shower is not working, immediately check whether the emergency switch of the outdoor box of the air shower is cut off. If it is confirmed to be cut off, press it gently with your hand, rotate it to the right, and let go.
     3. When the fan of the air shower room is reversed or the wind speed of the air shower room is very low, please be sure to check whether the 380V three-phase four-wire circuit is reversed. Generally, the air shower manufacturer will have a dedicated electrician to connect the wires when it is installed at the factory; if it is reversed, If the line source of the air shower is connected, the air shower fan will not work or the wind speed of the air shower will decrease, or the circuit board of the entire air shower will be burned. It is recommended that companies using air showers do not do so lightly. If you want to replace the wiring, please consult the air shower manufacturer to solve the problem if it is determined to be moved due to production needs.
     4. The air shower does not blow. In addition to the above three points, it is also necessary to check whether the emergency stop button inside the air shower box is pressed. If the emergency stop button is in color, the air shower will not blow; It can work normally if you press the emergency stop button again.
     5. When the air shower room cannot automatically sense and blow the air, please check the light sensor system in the lower right corner of the box in the air shower room to see if the light sensor device is installed correctly. If the two sides of the light sensor are opposite and the light sensitivity is normal, the air shower room can automatically sense and blow the air. Rain.
     6. When the wind speed of the air shower room is very low after being used for some time, please check whether the primary and high-efficiency filters of the air shower room have excessive dust accumulation. If so, please replace the filter. (The primary filter in the air shower is usually replaced every 1-6 months, and the high-efficiency filter in the air shower is usually replaced every 12-24 months).