German French Italian Portuguese Japanese Korrean Russian
Home

News

Air shower room fault disposal and maintenance

Air shower room fault disposal and maintenance

      Air shower room fault disposal.
      1. When the air shower room is used for some time if the wind speed is very low, you should immediately check whether the air shower room filter can accumulate too much dust, such as a new replacement filter. Usually 1-6 months it is necessary to exchange once, high-efficiency filter is usually 6-12 months to exchange once.
      2. If the air shower room can not automatically sense the blowing shower, check the light sensor system in the lower right corner of the box inside the air shower room, to see if the light sensor equipment can be equipped correctly. If the emergency stop key is red, it means that the air shower room will not blow shower, just need to press the emergency stop key from the beginning of normal operation.
      3 when the wind shower room does not work, the first check for a bad situation shower door outside the box of the urgent switch can be blocked, if blocked, with a hand quietly press, and rotate to the right to let go.
      4, wind showers treasure fan reversal or wind shower room wind speed is very small, it is necessary to check - under the 380V three-phase four-wire line can be connected to the reverse. If the reverse connection of the line source of the air shower room, the light will cause the air shower fan not to work or reverse air shower room wind speed reduction, the heavy will burn the entire air shower room circuit board.
      Nine maintenance.
      1, the regular use of instruments to determine the technical indicators of the equipment, such as does not meet the requirements of the technical parameters should be dealt with promptly
      2、According to the actual use of the situation, the regular primary air filter in the filter material was removed to clean.
      3, when the wind speed is found to become small, you should first check whether the surface of the primary air filter is blackened, if blackened, it means that the pre-fluidizer holds more dust and the yang force increases, which means that the non-woven fabric in the primary air filter should be removed for cleaning or replacement.
      When the non-woven fabric is replaced or cleaned, the wind speed still cannot be increased, which means that the high-efficiency air filter has been clogged, increasing Yang Li, and the high-efficiency air filter should be replaced. 5. When replacing the high-efficiency filter, the spray ball plate should be removed, and the high-efficiency filter should be replaced by the specifications of the original high-efficiency air filter. When installing, confirm that the arrow of the simple head marking of the high-efficiency filter should point to the direction of the airflow. And ensure good sealing to prevent leakage.
      After the replacement of the high-efficiency filter, it is necessary to confirm that there is no leakage in the frame and test it with a dust particle counter to achieve the technical specifications before normal operation.
      7、Regularly overhaul the electrical line, if there is any fault, you can refer to the electrical schematic diagram for maintenance.
      8, regular enclosure of the door, so that the electronic lock and its lock hole are aligned so as not to lock the pin jammed.
      9, the use of temperature shall not exceed 50 ° C, the use of open flame is strictly prohibited.